DN-60791:A • 10/1/13 — Page 1 of 2
8100(A)
Conventional FAAST Fire Alarm
Aspiration Sensing Technology®
Conventional Smoke Detector
DN-60791:A
General
The FAAST 8100(A) conventional aspirating smoke detector
combines dual-source (blue LED and infrared laser) optical
smoke detection with advanced algorithms to detect a wide
range of fires while maintaining enhanced immunity to nui-
sance particulates. This enables the 8100 to accurately detect
incipient fire conditions as early as 30 to 60 minutes before a
fire actually starts for Early Warning Fire Detection and Very
Early Warning Fire Detection. For initial system creation, the
PipeIQ
® software guides users through pipe layout. The soft-
ware also provides intuitive control over system configuration
and ongoing system monitoring. An installed device can be
monitored through its integral display, from a computer con-
nected to the device, or remotely through a computer browser
or mobile device when the detector is connected to a network,
or by Modbus/TCP protocol over Ethernet. When Internet-con-
nected, the 8100 can also e-mail status updates to appropriate
personnel. The detector can communicate alarm levels, urgent
and minor faults, and isolate inputs via eight form C relays. To
enable a full detection strategy, the 8100combines its
advanced communications capabilities with an extensive
range of customizable settings. The detector provides five
alarm levels that can be programmed for latching or non-latch-
ing relays. To accommodate specific codes or environments,
alarm delays can be set anywhere between 0 to 60 seconds.
The 8100 also supports two sensitivity modes: In Acclimate
mode, the detector automatically adjusts itself to current envi-
ronmental conditions to reduce nuisance alarms. Day/Night/
Weekend mode enables technicians to preset alarm thresh-
olds based on routine changes in the environment.
Features
Detection as precise as 0.00046%/ft obscuration.
Five alarm levels and two sensitivity modes provide applica-
tion flexibility.
Dual flow detection including both ultrasonic and electronic
sensing for pipe and chamber air flow measurement.
A single device protects up to 8,000 square feet.
Advanced detection algorithms reject common nuisance
conditions.
Patented particle separator and field-replaceable filter
remove contaminants from the system.
PipeIQ™ software provides intuitive system layout, configu-
ration, and monitoring all in one package.
Using the onboard Ethernet interface, you can monitor the
detector from any Internet browser, smart phone or mobile
device with VPN capability. You can also configure the
detector to e-mail status updates to appropriate personnel.
Monitoring and configuration can also be accomplished
using Modbus/TCP protocol over Ethernet.
Fault indicators exhibit a broad spectrum of events.
Unique air flow pendulum graph verifies pipe network func-
tionality.
Particulate graph displays subtle environmental changes for
early problem indications.
5 programmable alarm levels for latching or non-latching as
well as a 0 to 60 second delay to best accommodate local
codes or environments.
At startup 8100 self-adapts to its environment in just 24
hours, not weeks. The exclusive Acclimate mode automati-
cally adjusts within your specified parameters to reduce nui-
sance alarms and adjust to current conditions.
Comprehensive, simple and intuitive display has real-time,
quick-read information at the device including five alarm
levels, ten particulate levels, air flow, power and a wide
range of faults to quickly identify the problem for prompt
correction.
Specifications
ELECTRICAL SPECIFICATIONS
External Supply Voltage: 18-30 VDC.
Remote Reset Time: External monitor must be pulled low for
a minimum of 100 ms.
Power Reset: 1 sec.
Avg. Operating Current: 500 mA @ 24 VDC.
Alarm: 650 mA – All relays active, all alarm levels displayed.
Voltage @ 24 VDC.
Relay Contact Ratings: 3.0 A @ 30 VDC, 0.5 A @ 125 VAC.
ENVIRONMENTAL RATINGS
Operating Temperature: 32°F (0°C) to 100°F (38°C).
Sampled Air Temperature: -4°F (-20°C) to 140°F (60°C).
Humidity Range: 10 to 95% (non-condensing).
IP Rating: IP30.
Coverage Area: 8,000 sq. ft. (743 sq. m).
Air Movement: 0-4,000 ft./min (0-1,219 m/min).
Vue de la page 0
1 2

Résumé du contenu

Page 1 - Specifications

DN-60791:A • 10/1/13 — Page 1 of 28100(A)Conventional FAAST Fire Alarm Aspiration Sensing Technology®Conventional Smoke DetectorDN-60791:AGeneralThe F

Page 2 - Product Line Information

Page 2 of 2 — DN-60791:A • 10/1/13NOTIFIER®, FlashScan®, PipeIQ®, and FAAST Fire Alarm AspirationSensing Technology® are registered trademarks of and

Commentaires sur ces manuels

Pas de commentaire