dn-7114:c • 5/22/09 — Page 1 of 2
N-ANN-80
80-Character LCD
Serial Annunciator
Annunciators
dn-7114:c • A1-65
7114cov.jpg
General
The N-ANN-80 annunciator is a compact, backlit, 80-character
LCD fire annunciator that mimics the Fire Alarm Control Panel
(FACP) display. It provides system status indicators for AC
Power, Alarm, Trouble, Supervisory, and Alarm Silenced condi-
tions. The N-ANN-80 and the FACP communicate over a two-
wire serial interface employing the ANN-BUS communication
format. Connected devices are powered, via two
additional
wires, by either the host FACP or a remote UL-listed, filtered
power supply.
N-ANN-80 is black; for white order N-ANN-80-W.
The N-ANN-80 displays English-language text of system point
information including device type, zone, independent point
alarm, trouble or supervisory status, as well as any custom
alpha labels programmed into the control panel. It includes con-
trol switches for remote control of critical system functions. (A
keyswitch prevents unauthorized operation of the control
switches.)
Up to eight N-ANN-80s may be connected to the ANN-BUS of
each FACP. Minimal programming is required, which saves time
during system commissioning. The N-ANN-80 is compatible
with NOTIFIER FACPs with an ANN-BUS, such as the NFW-50.
Features
Listed to UL Standard 864, 9th Edition.
Backlit 80-character LCD display (20 characters x 4 lines).
Mimics all display information from the host panel.
Control switches for System Acknowledge, Signal Silence,
Drill, and Reset.
Control switches can be independently enabled or disabled
at the FACP.
Keyswitch enables/disables control switches and mechani-
cally locks annunciator enclosure
Keyswitch can be enabled or disabled at the FACP.
Enclosure supervised for tamper.
System status LEDs for AC Power, Alarm, Trouble, Supervi-
sory, and Alarm Silence.
Local sounder can be enabled or disabled at the FACP.
N-ANN-80 connects to the ANN-BUS terminal on the FACP
and requires minimal panel programming.
Displays device type identifiers, individual point alarm, trou-
ble, supervisory, zone, and custom alpha labels.
Time-and date display field.
Surface mount directly to wall or to single, double, or 4"
square electrical box.
Semi-flush mount to single, double, or 4" square electrical
box. Use ANN-SB80KIT for angled view mounting.
Can be remotely located up to 6,000 feet (1,800 m) from the
panel.
Backlight turns off during AC loss to conserve battery power
but will turn back on if an alarm condition occurs.
May be powered by 24 VDC from the host FACP or by remote
power supply (requires 24 VDC).
Up to eight N-ANN-80s can be connected on the ANN-BUS.
Controls and Indicators
•AC Power
•Alarm
•Trouble
Supervisory
Alarm Silenced
Specifications
Operating voltage range: 18 VDC to 28 VDC.
Current consumption @ 24 VDC nominal (filtered and non-
resettable): 40 mA maximum.
Ambient temperature: 32°F to 120°F (0°C to 49°C).
Relative humidity: 93% ± 2% RH (noncondensing) at 32°C
± 2°C (90°F ± 3°F).
5.375” (13.65 cm.) high x 6.875” (17.46 cm.) wide x 1.375”
(3.49 cm.) deep.
For use indoors in a dry location.
All connections are power-limited and supervised.
Agency Listings and Approvals
The listings and approvals below apply to the N-ANN-80. In
some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory
for latest listing status.
UL: S635
•FM approved
CSFM: 7120-0028:240
MEA: 442-06-E Vol. 2
The ANN-BUS
POWERING THE DEVICES ON THE ANN-BUS FROM
AUXILIARY POWER SUPPLY
The ANN-BUS can be powered by an auxiliary power supply
when the maximum number of ANN-BUS devices exceeds the
ANN-BUS power requirements. See the FACP manual for more
information.
Vue de la page 0
1 2

Résumé du contenu

Page 1 - N-ANN-80

dn-7114:c • 5/22/09 — Page 1 of 2N-ANN-8080-Character LCD Serial AnnunciatorAnnunciatorsdn-7114:c • A1-657114cov.jpgGeneralThe N-ANN-80 annunciator is

Page 2 - FACP Wiring to ANN-BUS Device

Page 2 of 2 — dn-7114:c • 5/22/09©2009 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.Th

Commentaires sur ces manuels

Pas de commentaire