Page 2 of 4 — DN-7087:C1 • 11/9/11
STROBE
The strobe shall be a System Sensor SpectrAlert Advance
Model _______ listed to UL 1971 and shall be approved for fire
protective service. The strobe shall be wired as a primary-sig-
naling notification appliance and comply with the Americans
with Disabilities Act requirements for visible signaling appli-
ances, flashing at 1 Hz over the strobe’s entire operating volt-
age range. The strobe light shall consist of a xenon flash tube
and associated lens/reflector system.
HORN/STROBE COMBINATION
The horn/strobe shall be a System Sensor SpectrAlert
Advance Model _______ listed to UL 1971 and UL 464 and
shall be approved for fire protective service. The horn/strobe
shall be wired as a primary-signaling notification appliance
and comply with the Americans with Disabilities Act require-
ments for visible signaling appliances, flashing at 1 Hz over the
strobe’s entire operating voltage range. The strobe light shall
consist of a xenon flash tube and associated lens/reflector sys-
tem. The horn shall have three audibility options and an option
to switch between a Temporal 3 pattern and a Non-Temporal
(continuous) pattern. These options are set by a multiple posi-
tion switch. On four-wire products, the strobe shall be powered
independently of the sounder. The horn on horn/strobe models
shall operate on a coded or non-coded power supply.
OUTDOOR PRODUCTS
SpectrAlert Advance outdoor horns, strobes and horn/strobes
shall be listed for outdoor use by UL and shall operate
between –40°F and 151°F (–40°C and 66°C). The products
shall be listed for use with a System Sensor outdoor/weather-
proof backbox with half-inch and three-fourths-inch conduit
entries.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit MDL3R or
MDL3W listed to UL 464 and shall be approved for fire protec-
tive service. The module shall synchronize SpectrAlert strobes
at 1 Hz and horns at Temporal 3. Also, while operating the
strobes, the module shall silence the horns on horn/strobe
models over a single pair of wires. The module shall mount to
a 4.688" x 4.688" x 2.125" (11.906 x 11.906 x 5.398 cm) back-
box. The module shall also control two Style Y (class B) cir-
cuits or one Style Z (Class A) circuit. The module shall
synchronize multiple zones. Daisy-chaining two or more syn-
chronization modules together will synchronize all the zones
they control. The module shall not operate on a coded power
supply.
Operating Specifications
• Standard operating temperature: 32°F to 120°F (0°C to
49°C).
• K Series operating temperature: –40°F to 151°F (–40°C
to 66°C).
• Humidity range: 10% to 93% non-condensing (indoor
products).
• Strobe flash rate: 1 flash per second.
• Nominal voltage: regulated 12 VDC/FWR or regulated 24
VDC/FWR. NOTE: Full Wave Rectified (FWR) voltage is a
non-regulated, time-varying power source that is used on
some power supply and panel outputs.
• Operating voltage range: 8 V to 17.5 V (12 V nominal); or
16 V to 33 V (24 V nominal). NOTE: P, S, PC, and SC prod-
ucts will operate at 12 V nominal only for 15 cd and 15/75
cd.
• Input terminal wire gauge: 12 to 18 AWG (3.31 to 0.821
mm²).
• Ceiling-mount dimensions (including lens): 6.8" diame-
ter x 2.5" deep (17.3 cm diameter x 6.4 cm deep).
• Wall-mount dimensions (including lens): 5.6" H x 4.7" W
x 2.5" D (14.2 cm H x 11.9 cm W x 6.4 cm D).
• Horn dimensions: 5.6" H x 4.7" W x 1.3" D (14.2 cm H x
11.9 cm W x 3.3 cm D).
Agency Listings and Approvals
The listings and approvals below apply to SpectrAlert Advance
Selectable Output Notification Devices. In some cases, certain
modules may not be listed by certain approval agencies, or
listing may be in process. Consult factory for latest listing sta-
tus.
• UL Listed: S4011 (HR__, HW__, P2__, P4__, PC2__,
PC4__ models); S5512 (models SCR, SCRH, SCW,
SCWH, SR, SRH, SW, SWH); S3593 (SCRHK, SCRK,
SRHK, SRK).
• ULC Listed: S4011 (HRA, HRKA); S5512 (typically “A”
models, with exception of outdoor strobes). See Canadian
data sheet for listings and specifications.
• FM approved
• MEA: 452-05-E
• CSFM: 7125-1653:0186 (SCR, SCRH, SCW, SCWH, SR,
SRH, SW, SWH); 7300-1653:0188 (P2_, P4_, PC2_, PC4_
modules); 7135-1653:0189 (HR, HRK, HW); 7300-
1653:0187 (SCRHK, SCRK, SRHK, SRK).
Strobe Current Draw,
UL Maximum (mA RMS)
Candela
8 – 17.5 V 16 – 33 V
DC FWR DC FWR
Standard
Candela
Range
15 123 128 66 71
15/75 142 148 77 81
30 NA N/A 94 96
75 NA NA 158 153
95 NA NA 181 176
110 NA NA 202 195
115 NA NA 210 205
High
Candela
Range
135 NA NA 228 207
150 NA NA 246 220
177 NA NA 281 251
185 NA NA 286 258
Horn Current Draw,
UL Maximum (mA RMS)
Sound
Pattern
dB
8 – 17.5 V 16 – 33 V
DC FWR DC FWR
Temporal High 57 55 69 75
Temporal Medium 44 49 58 69
Temporal Low 38 44 44 48
Non-temporal High 57 56 69 75
Non-temporal Medium 42 50 60 69
Non-temporal Low 41 44 50 50
Coded High 57 55 69 75
Coded Medium 44 51 56 69
Coded Low 40 46 52 50