Notifier XP10-M 10 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Sécurité Notifier XP10-M 10. Notifier XP10-M 10 User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 2
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
DN-6923:B • 05/15/2009 — Page 1 of 2
XP10-M(A)
Ten-Input Monitor Module
Addressable Devices
DN-6923:B • H-352
General
The XP10-M ten-input monitor module is an interface
between a control panel and normally open contact devices
in intelligent alarm systems such as pull stations, security
contacts, or flow switches.
The first address on the
XP10-M
is set from 01 to 150 and
the remaining modules are automatically assigned to the
next nine higher addresses. Provisions are included for dis-
abling a maximum of two unused addresses.
The supervised state (normal, open, or short) of the moni-
tored device is sent back to the panel. A common SLC input
is used for all modules, and the initiating device loops share a
common supervisory supply and ground — otherwise each
monitor operates independently from the others.
Each XP10-M module has panel-controlled green LED indi-
cators. The panel can cause the LEDs to blink, latch on, or
latch off.
NOTE: Unless otherwise specified, the term XP10-M is used in
this data sheet to refer to both the XP10-M and the XP10-MA
(ULC-listed version)
.
Features
Listed to UL Standard 864, 9th edition.
Ten addressable Class B or five addressable Class A initi-
ating device circuits.
Removable 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²)
plug-in terminal blocks.
Status indicators for each point.
Unused addresses may be disabled.
Rotary address switches.
Class A or Class B operation.
FlashScan® or CLIP operation.
Flexible mounting options.
Mounting hardware included.
Specifications
Standby current: 3.5 mA (SLC current draw with all
addresses used; if some addresses are disabled, the
standby current decreases).
Alarm current: 55 mA (assumes all ten LEDs solid ON).
Temperature range: 32°F to 120°F (0°C to 49°C) for UL
applications; –10°C to +55°C for EN54 applications.
Humidity: 10% to 85% noncondensing for UL applications;
10% to 93% noncondensing for EN54 applications.
Dimensions: 6.8" (172.72 mm) high x 5.8" (147.32 mm)
wide x 1.25" (31.75 mm) deep.
Shipping weight: 0.76 lb. (0.345 kg) including packaging.
Mounting options:
CHS-6 chassis: Up to 6 modules.
BB-25 cabinet: Up to 6 modules.
BB-XP cabinet: One or two modules.
CAB-4 Series cabinet: See DN-6857.
EQ Cabinet Series: See DN-60229.
Wire gauge: 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²).
Power-limited circuits must employ type FPL, FPLR, or
FPLP cable as required by Article 760 of the NEC.
XP10-M is shipped in Class B position; remove shunt for
Class A operation.
Maximum SLC wiring resistance: 40 or 50 ohms, panel
dependent.
Maximum IDC wiring resistance: 1500 ohms.
Maximum IDC voltage: 10.2 VDC.
Maximum IDC current: 240 µA.
Agency Listings and Approvals
The listings and approvals below apply to the XP10-M(A) Ten-
Input Monitor Module. In some cases, certain modules or
applications may not be listed by certain approval agencies, or
listing may be in process. Consult factory for latest listing
status.
UL Listed: S635
ULC Listed: S635 (XP10-MA)
CSFM approved: 7300-0028:219
•FM approved
MEA approved: 43-02-E
Maryland State Fire Marshal approved: Permit #2106
6923xp10.jpg
Vue de la page 0
1 2

Résumé du contenu

Page 1 - XP10-M(A)

DN-6923:B • 05/15/2009 — Page 1 of 2XP10-M(A)Ten-Input Monitor ModuleAddressable DevicesDN-6923:B • H-352GeneralThe XP10-M ten-input monitor module i

Page 2 - Product Line Information

Page 2 of 2 — DN-6923:B • 05/15/2009FlashScan® and NOTIFIER® are registered trademarks of HoneywellInternational Inc. Microsoft® and Windows® are reg

Commentaires sur ces manuels

Pas de commentaire